    Cooling Tower Chemical Treatment: Antiscalant, Biocide & Corrosion Control

    How to calculate blowdown rates and dose antiscalants, biocides, and corrosion inhibitors in industrial cooling towers.

    Dr. Sarah Johnson
    Technical Director
    Cooling Tower Chemical Treatment: Antiscalant, Biocide & Corrosion Control

    Cooling towers are the lungs of an industrial plant. Without proper chemical treatment, they quickly succumb to scale, corrosion, and biological fouling (like Legionella).

    Engineering Calculation: Cooling Tower Blowdown

    Scenario: Circulation rate 1,000 m³/hr, Temp drop 10°C

    Evaporation ≈ 1% of circulation for every 5.5°C drop
    Evaporation % = (10 / 5.5) × 1% = 1.82%
    Evaporation flow = 1,000 × 1.82% = 18.2 m³/hr

    Operating at 5 cycles of concentration:
    Blowdown = Evaporation / (Cycles - 1)
    Blowdown = 18.2 / (5 - 1) = 4.55 m³/hr

    Make-up water = Evaporation + Blowdown = 22.75 m³/hr (22,750 L/hr)

    Chemical Dosing (e.g., 30 ppm into make-up):
    30 ppm = 30 mg/L
    Chemical mass = 22,750 × 30 = 682,500 mg/hr = 0.6825 kg/hr
    Daily chemical requirement = 16.38 kg/day

    Water Treatment Chemicals